The CR-135EWT is a combination rate-of-rise and fixed temperature detector in a case aluminum housing suitable for use in the hazardous locations described above. A set of normally open contacts will close when the ceiling temperature increases at a minimum rate of 15°F (8.4°C) per minute. Closing the contact initiates the direct alarm sequence. Independent of the rate-of-rise operation, the fixed temperature portion consists of a spring-loaded plunger retained by a fusible alloy that releases when the ceiling temperature reaches 135°F (57°C). When released, the plunger strikes the set of contacts and holds them closed. Spacing between detectors on an uninterrupted ceiling is 50 ft. (15.2m) for the rate-of-rise and 30 ft. (9.1m) for the fixed temperature portion. Distance from any wall or partition is 25 ft. (7.5m) and 15 ft. (4.5m) respectively.
Need help in finding the right Heat Detector ? Give us a call toll free at (800)447-0387, Monday to Friday from 8AM to 5PM. Our Sales Team will be happy to answer any of your questions. Need to reach us after hours? Contact Us electronically. Be sure to enter your phone number for a prompt response.
Warranty Information
This product has a 1 Year Warranty. Warranty is Provided by Potter